Superheat and subcooling at startup, in plain words

The StartupSend teamNovember 20267 min read

A unit can blow cold air and still be charged wrong. Superheat and subcooling are the two numbers that show whether the refrigerant side is right, and they take two minutes once the unit has settled. Here is what they mean, how to take them, and what they point to.

What they are

Superheat is how many degrees the refrigerant vapor has warmed past its boiling point by the time it leaves the evaporator. You measure it on the suction line.

Subcooling is how many degrees the liquid has cooled below its condensing point by the time it leaves the condenser. You measure it on the liquid line.

The boiling and condensing points come from the pressure: every refrigerant boils at a set temperature for a given pressure. That is what a pressure and temperature chart (or the scale on your gauges) tells you, and why you need to know which refrigerant is in the unit.

Taking the readings

  1. Run the unit in cooling long enough for the pressures to settle. The manufacturer's instructions say how long; 10 to 15 minutes is common.
  2. Note the refrigerant from the nameplate, and record the outdoor temperature and the entering air temperature at the unit.
  3. Read the suction pressure at the suction service port, and the suction line temperature with a clamp probe on the line near that port. Insulate the probe from the air around it.
  4. Read the liquid line pressure (or the discharge pressure, if that is where the unit's port is and the manufacturer's charts use it), and the liquid line temperature near the liquid service port.

The math

Superheat = suction line temperature minus the saturation temperature for the suction pressure.

Subcooling = the saturation temperature for the liquid pressure minus the liquid line temperature.

A worked example with R-410A

Suction pressure118 psig
Saturation temperature at 118 psigabout 40°F
Suction line temperature51°F
Superheat: 51 minus 4011°F
Liquid pressure365 psig
Saturation temperature at 365 psigabout 110°F
Liquid line temperature100°F
Subcooling: 110 minus 10010°F
Blends with glide: some refrigerants, such as R-407C, boil across a range of temperatures instead of at one point. For those, use the dew point for superheat and the bubble point for subcooling. Your chart or gauges list both.

Which one to charge by

It depends on the metering device:

  • Fixed orifice or piston: charge by superheat. The target comes from the manufacturer's chart, using the indoor wet bulb and the outdoor temperature.
  • TXV or electronic expansion valve: charge by subcooling. The valve holds the superheat steady on its own, so subcooling is the number that moves with the charge. The target is on the nameplate or in the instructions.

Heat pumps are usually checked in cooling mode. When the weather makes that impossible, follow the manufacturer's procedure for heating mode or weighing in the charge.

What the numbers point to

These patterns tell you where to look first. They are not a diagnosis on their own.

SuperheatSubcoolingPoints to
HighLowLow charge, or a leak
LowHighToo much charge
HighHighA restriction: the filter drier, the liquid line or the metering device
LowNormalOn a fixed orifice, low airflow across the indoor coil: filters, belt, a dirty coil, fan speed

What a good report shows

All four readings, both results, the refrigerant, and the conditions they were taken in. A report that only says "SH 11, SC 10" asks the commissioning provider to trust the math. A report with the pressures and temperatures lets them check it in ten seconds, and that is the one that gets approved.